8-Channel Power Relay Output PoE Module

 

Реле  
Количество каналов 8
Тип выхода Power Relay, Form A (SPST N.O.)
Operating Voltage Range 250 VAC/30 VDC
Max. ток нагрузки 5.0 A/channel at 25 °C
Время срабатывания 6 ms (Typical)
Время отсоединения 3 ms (Typical)
Электрический ресурс срабатываний ( VDE )
5A 250 VAC 30,000 ops (10 ops/minute) at 75 °C
5A 30 VDC 70,000 ops (10 ops/minute) at 75 °C
Электрический ресурс срабатываний ( UL )
5A 250 VAC/30 VDC 6,000 ops.
3A 250 VAC/30 VDC 10,000 ops.
Механический ресурс срабатываний 20,000,000 ops. at no load (300 ops./minute)
System  
Процессор 16-bit CPU
SRAM 512 KB
Flash Memory 512 KB
EEPROM 16 KB
Сторожевой таймер Да
Интерфейсы  
PoE Ethernet Port 10/100 Base-TX (With Link, Activity LED Indicator) and automatic MDI/MDI-X
2 Way Isolation  
I/O 3000 Vrms
EMS Protection  
ESD (IEC 61000-4-2) 4 kV Contact for each terminal
EFT (IEC 61000-4-4) +/-2 kV for Power
LED Indicators  
PoE PoE On
L1 System Running
L2 Ethernet Link/Act
L3 Ethernet 10/100M Speed
Power Requirements  
Reserve Polarity Protection Да
Powered from terminal block Yes, 12 ~ 48 VDC
Powered from PoE Yes, IEEE 802.3af, Class1
Consumption 5.3 W
Mechanical  
Dimensions (W x H x D) 72 mm x 123 mm x 35 mm
Installation DIN-Rail or Wall mounting
Environment  
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, non-condensing
Functions  
Rule Configuration Website Access Web server on WISE controllers to edit and upload logic rules through web browser.
36 IF-THEN-ELSE Logic Rules 3 IF conditions with AND or OR operators 3 THEN actions and 3 ELSE actions
48 Internal Registers Hold temporary variables and read/write data via Modbus/TCP address.
12 Timers Delay / Timing functions
12 Emails Send Email messages to pre-set Email receivers.
12 CGI Commands Send pre-set CGI commands.
12 Recipes Set up THEN/ELSE action groups.
8 P2P remote modules Set up the connection information for the remote WISE modules.
Modbus/TCP Protocol Real time control and monitoring I/O channels and system status of controllers via SCADA software.
IF Conditions  
Internal Register =, <, >, >=, <= (value)
DO Counter =, >, <, >=, <=(value), Change
Timer Timeout, Not Timeout
P2P DI, AI, DI counter, DO counter, IR
Rule Status Enable, Disable
THEN / ELSE Actions  
DO Channel ON, OFF, Pulse Output
Internal Register Change the value
DO Counter Reset
Timer Start, Stop
Email Send
CGI Commands Send
Recipe Execute
P2P DO(On/Off), AO, IR
Rule Status Enable, Disable

 